In an
electrical grid An electrical grid (or electricity network) is an interconnected network for electricity delivery from producers to consumers. Electrical grids consist of power stations, electrical substations to step voltage up or down, electric power tran ...
, the short circuit ratio (or SCR) is the ratio of: the short circuit
apparent power In an electric circuit, instantaneous power is the time rate of flow of energy past a given point of the circuit. In alternating current circuits, energy storage elements such as inductors and capacitors may result in periodic reversals of the d ...
(SCMVA) in the case of a line-line-line-ground (3LG) fault at the location in the grid where some generator is connected, to: the power rating of the generator itself (GMW). Since the power that can be delivered by the grid varies by location, frequently a location is indicated, for example, at the point of interconnection (POI): :SCR_ = \frac SCR is used to quantify the system strength of the grid (its ability to deal with changes in active and reactive power injection and consumption). On a simplified level, a high SCR indicates that the particular generator represents a small portion of the power available at the point of its connection to the grid, and therefore the generator problems cannot affect the grid in a significant way. SCMVA is defined as a product of the voltage before the 3LG fault and the current that would flow after the fault (this worst-case combination will not happen in practice, but provides a useful estimation of the capacity of the circuit). SCMVA is also called a short circuit level (SCL), although sometimes the term SCL is used to designate just the short-circuit current.


Grid strength

The term grid strength (also system strength) is used to describe the resiliency of the grid to the small changes in the vicinity of the grid location (“grid stiffness”). From the side of an electrical generator, the system strength is related to the changes of voltage the generator encounters on its terminals as the generator's current injection varies. Therefore, the quantification of the system strength can be done through finding the equivalent ( Thévenin)
electrical impedance In electrical engineering, impedance is the opposition to alternating current presented by the combined effect of Electrical_resistance, resistance and Electrical_reactance, reactance in a electrical circuit, circuit. Quantitatively, the impedan ...
of the system as observed from these terminals (the strength is inversely proportional to the resistance). SCR and its variations provide a convenient way to calculate this impedance under normal or contingency conditions (these estimates are not intended for the actual short-circuit state). Strong grids provide a reliable reference for power sources to synchronize. In a very stiff system the voltage does not change with variations of the power injected by a particular generator, making its control simpler. In a traditional grid dominated by synchronous generators, a strong grid with SCR greater than 3.0 will have the desired voltage stability and active power reserves. A weak grid (with SCR values between 2.0 and 3.0) can exhibit voltage instability and control problems. A grid with SCR below 2.0 is ''very weak''.


Importance of overcurrent

Grid strength is also important for its
overcurrent In an electric power system, overcurrent or excess current is a situation where a larger than intended electric current exists through a conductor, leading to excessive generation of heat, and the risk of fire or damage to equipment. Possible caus ...
capabilities that are essential for the power system operations. Lack of overcurrent capability (low SCR) in a weak grid creates a multitude of problems, including: * transients during the large load changes will cause large variations of the grid voltage, causing problems with the loads (e.g., some motors might not be able to start in the undervoltage condition); * the grid protection devices are designed to be triggered by a sufficient level of overcurrent. In a weak system the short circuit current might be hard to distinguish from a normal transient overcurrent encountered during the load changes; * during a
black start A black start is the process of restoring an electric power station, a part of an electric grid or an industrial plant, to operation without relying on the external transmission network, electric power transmission network to recover from a tota ...
operation after a
power outage A power outage, also called a blackout, a power failure, a power blackout, a power loss, a power cut, or a power out is the complete loss of the electrical power network supply to an end user. There are many causes of power failures in an el ...
, large inrush current might be needed to energize the system components. For example, if some loads in a weak system remain connected, an
inverter-based resource An inverter-based resource (IBR) is a source of electricity that is asynchronously connected to the electrical grid via an electronic power converter ("inverter"). The devices in this category, also known as converter interfaced generation (CIG) a ...
might not be able to start.


Presence of inverter-based resources

Large penetration of the
inverter-based resource An inverter-based resource (IBR) is a source of electricity that is asynchronously connected to the electrical grid via an electronic power converter ("inverter"). The devices in this category, also known as converter interfaced generation (CIG) a ...
s (IBRs) reduces the short circuit level: a typical synchronous generator can deliver a significant
overcurrent In an electric power system, overcurrent or excess current is a situation where a larger than intended electric current exists through a conductor, leading to excessive generation of heat, and the risk of fire or damage to equipment. Possible caus ...
, 2-5 p.u., for a relatively long time (minutes), while the component limitations of the IBRs result in overcurrent limits of less than 2 p.u. (usually 1.1-1.2 p.u.). The original SCR definition above was intended for a system with predominantly synchronous generation, so multiple alternative metrics, including ''weighted short circuit ratio'' (WSCR), ''composite short circuit ratio'' (CSCR), ''equivalent circuit short circuit ratio'' (ESCR), and ''short circuit ratio with interaction factors'' (SCRIF), have been proposed for the grids with multiple adjacent IBRs to avoid an overestimation of the grid strength (an IBR relies on grid strength to synchronize its operation and does not have much overcurrent capacity). Henderson et al. argue that in case of IBRs the SCR and system strength are in fact decoupled and propose a new metric, ''grid strength impedance''. Integrating renewable energy sources often raises concerns about the system's strength. The ability of different components in a
power system An electric power system is a network of electrical components deployed to supply, transfer, and use electric power. An example of a power system is the electrical grid that provides power to homes and industries within an extended area. The e ...
to perform effectively depends on the system's strength, which measures the system variables' sensitivity to disturbances. The short circuit ratio (SCR) is an indicator of the strength of a network bus about the rated power of a device and is frequently used as a measure of system strength. A higher SCR value indicates a stronger system, meaning that the impact of disturbances on voltage and other variables will be minimized. A strong system is defined as having an SCR above three, and the SCRs of weak and very weak systems range between three and two and below two, respectively. Power electronic applications often encounter issues related to SCR, particularly in renewable energy systems that use power converters to connect to power grids. When connecting HVDC/FACTs devices based on current source converters to weak AC systems, particular technologies must be employed to overcome SCR of less than three. For
HVDC A high-voltage direct current (HVDC) electric power transmission system uses direct current (DC) for electric power transmission, in contrast with the more common alternating current (AC) transmission systems. Most HVDC links use voltages betwe ...
, voltage-source-based converters or capacitor-commutated converters are utilized in applications with SCR near one. Failing to use these technologies will require special studies to determine the impact and take measures to prevent or minimize the adverse effects, as low levels of SCR can cause problems such as high over-voltages, low-frequency resonances, and instability in
control systems A control system manages, commands, directs, or regulates the behavior of other devices or systems using control loops. It can range from a single home heating controller using a thermostat controlling a domestic boiler to large industrial co ...
. Wind farms are commonly linked to less robust network sections away from the main power consumption areas. Problems with voltage stability that arise from incorporating large-scale wind power into vulnerable systems are crucial issues that require attention. Some wind turbines have specific minimum system strength criteria. GE indicates that the standard parameters of their wind turbine model are appropriate for systems with a Short Circuit Ratio (SCR) of five or higher. However, if connecting to weaker systems, it is necessary to carry out further analysis to guarantee that the model parameters are adequately adjusted. Specifically designed control methods for wind turbines or dynamic reactive compensation devices, such as
STATCOM In electrical engineering , a static synchronous compensator (STATCOM) is a shunt-connected, voltage control and reactive power management, reactive compensation device used on transmission networks. It uses power electronics to form a voltage-sour ...
, are required to ensure optimal performance.


Example

An experience at
ERCOT The Electric Reliability Council of Texas, Inc. (ERCOT) is an American organization that operates Texas's electrical grid, the Texas Interconnection, which supplies power to more than 25 million Texas customers and represents 90 percent of the st ...
in early 21st century provides a prime example of how the wind turbine's performance is affected by a weak system strength. The wind power plant, linked to the ERCOT grid through two 69kV transmission lines, worked efficiently when the SCR was around 4 during normal operations. However, when one of the 69kV lines was disconnected, the SCR dropped to 2 or less, leading to unfavorable, poorly damped, or un-damped voltage oscillations that were documented by PMUs at the Point of Interconnection (POI) of the wind plant. After a thorough investigation, it was determined that the aggressive voltage control used by the WPP was not appropriate for a weak grid environment and was the primary cause of the oscillatory response. Due to the low short circuit level detected by the wind generator voltage controller and the high voltage control gain, the oscillation occurred. When compared to the normal grid with high SCR, the closed loop voltage control would have a faster response under weak grid conditions. To replicate the oscillatory response, the event was simulated using a detailed dynamic model representing the WPP.


Impact on grid

The SCR can be calculated for each point on an
electrical grid An electrical grid (or electricity network) is an interconnected network for electricity delivery from producers to consumers. Electrical grids consist of power stations, electrical substations to step voltage up or down, electric power tran ...
. A grid with high SCR is known as a strong grid or power system. A power system (grid) having a low SCR has more vulnerability to grid voltage instability. Hence such a grid or system is known as a weak grid or a weak power system. Grid strength can be increased by installing
synchronous condenser In electrical engineering, a synchronous condenser (sometimes called a syncon, synchronous capacitor or synchronous compensator) is a DC-excited synchronous motor, whose shaft is not connected to anything but spins freely. Its purpose is not to c ...
s. Condenser can act as a synchronous voltage source to support transient reactance and sub-transient reactance, also providing the
inertial response Inertial response is a property of large synchronous generators, which contain large synchronous rotating masses, and which acts to overcome any immediate imbalance between power supply and demand for electric power systems, typically the electric ...
and fault current contribution.
Static synchronous compensator In electrical engineering , a static synchronous compensator (STATCOM) is a shunt-connected, voltage control and reactive power management, reactive compensation device used on transmission networks. It uses power electronics to form a voltage-sour ...
s may also be used to improve the SCR ratio, being the current source limited by storage discharge and thermal condition.