Power system protection is a set of techniques and
power grid equipment used to limit the damage caused by an
electrical fault and safeguard other components of the grid, like
generators and
transmission lines. The term is also used for a branch of
electrical power engineering that deals with the protection. There is an overlap between the power system protection and
power system operations, as the protection equipment, like other
switchgear
In an electric power system, a switchgear is composed of electrical disconnect switches, fuses or circuit breakers used to control, protect and isolate electrical equipment. Switchgear is used both to de-energize equipment to allow work to ...
, can be used for operations.
The protection devices are used to protect the power systems from faults by detecting the faults and taking ''action'' ("tripping"). P. M. Anderson distinguishes the ''reactionary devices'', like
protective relays, that "clear" a fault by isolating it from the rest of system and ''safeguard devices'' that address the source of the hazard (for example, an
emergency core cooling system of a nuclear reactor). As a discipline, power system protection mostly deals with the reactionary devices.
Protection devices
Power system protection relies on few basic elements:
* a sensor performs a measurement (test) of a value (for example, of electric current in a transmission line);
* a comparator checks the test result against a ''threshold'' that the result is not supposed to cross during normal operation (for example, the maximum acceptable current value when testing for the
overcurrent condition). Ability to identify an abnormal condition is called ''sensitivity'';
* a timing element (''delay'') that checks for the persistence of the condition (for example, if a fault had been cleared by another protection device with a smaller delay setting, this device should not take any action);
* action element (typically
circuit-opening).
Protective devices include, under a common label of "
switchgear
In an electric power system, a switchgear is composed of electrical disconnect switches, fuses or circuit breakers used to control, protect and isolate electrical equipment. Switchgear is used both to de-energize equipment to allow work to ...
":
*
fuses are the simplest protection devices combining overcurrent sensing, delay, and action in a single circuit-opening fusible part;
*
protective relays sense the fault and initiate a trip, or disconnection, command;
*
power circuit breakers use commands from relays and autoreclosers to open/close the
electric circuit
An electrical network is an interconnection of electrical components (e.g., battery (electricity), batteries, resistors, inductors, capacitors, switches, transistors) or a model of such an interconnection, consisting of electrical elements (e. ...
. The breakers for the protective system are safe to open under a
fault current;
*
reclosers and
sectionalizers.
Connecting the protective devices to the grid usually involves additional hardware:
*
instrument transformers, both
current and
voltage
Voltage, also known as (electrical) potential difference, electric pressure, or electric tension, is the difference in electric potential between two points. In a Electrostatics, static electric field, it corresponds to the Work (electrical), ...
, are used to isolate the (mostly low-voltage) devices from the transmission levels;
*
electric batteries (with chargers) ensure operation in case of
power outage
A power outage, also called a blackout, a power failure, a power blackout, a power loss, a power cut, or a power out is the complete loss of the electrical power network supply to an end user.
There are many causes of power failures in an el ...
;
*
data communications
Data communication, including data transmission and data reception, is the transfer of data, signal transmission, transmitted and received over a Point-to-point (telecommunications), point-to-point or point-to-multipoint communication chann ...
to obtain the current and voltage at remote terminals of a line and to allow remote tripping of equipment.
With the exception of the breaker, the components of the protective device are frequently deployed in a
redundant fashion.
Protective zones

The objective of a protection scheme is to keep the power system stable by isolating only the components that are under fault, whilst leaving as much of the network as possible in operation, thus minimizing the
loss of load. This property of the protection system is called ''selectivity''. To achieve selectivity, the power system is subdivided into ''protective zones'', each containing a power system component that should be protected. Each zone has its own protection device(s) and provides sensitivity to faults within its boundaries. The boundaries of zones overlap to leave no part of grid without protection. The overlapping regions of sensitivity have a drawback of multiple relays possibly tripping when the fault is in the overlapped area. For example, unless special arrangements are made, a
short circuit
A short circuit (sometimes abbreviated to short or s/c) is an electrical circuit that allows a current to travel along an unintended path with no or very low electrical impedance. This results in an excessive current flowing through the circuit ...
above the relay A, but still within the blue zone on the diagram, might cause
overcurrent conditions in relays A, C, and D and cause them to trip, with the two latter trips being redundant. This can be avoided by using specialized relays (
distance
Distance is a numerical or occasionally qualitative measurement of how far apart objects, points, people, or ideas are. In physics or everyday usage, distance may refer to a physical length or an estimation based on other criteria (e.g. "two co ...
or
directional ones) or by coordinating the relay actions using a
communication channel
A communication channel refers either to a physical transmission medium such as a wire, or to a logical connection over a multiplexed medium such as a radio channel in telecommunications and computer networking. A channel is used for infor ...
("pilot").
Backup
The power protection system needs to be resilient to its own malfunctions. Thus it includes backup protection devices. For example if the fault is in the top left red zone, but outside the blue zone, it is expected to be handled by the "primary" relay A. If the relay A malfunctions and cannot clear the fault, the ''backup relays'' C and D in the adjacent (blue) zone will trip. This can be arranged without coordination (for example, the delay setting of C and D can be higher so they do not act if A succeeds in clearing the fault) or through coordination via a pilot. The term ''local backup'' is used when the backup relays are within the same zone as the "primary" one being duplicated.
Local back-up protection, like the primary protective device, will isolate the elements of the plant affected by the fault to clear the latter. Adjacent-zone ("remote") back-up protection will generally isolate both the affected and unaffected items of plant to clear the fault.
Fault types
The faults can be classified by their level of permanence that affects the possibility of
autoreclosing:
* a ''transient fault'' clears quickly once the line is opened (for example, a
flashover over an
insulator on the
transmission tower
A transmission tower (also electricity pylon, hydro tower, or pylon) is a tall structure, usually a lattice tower made of steel that is used to support an overhead power line. In electrical grids, transmission towers carry high-voltage transmis ...
caused by lightning). A quick reclosing with not cause the fault to reappear. The transient faults represent the vast majority of faults on the
overhead transmission lines;
* a ''semipermanent fault'', like
tree contact, are faults that might clear themselves if allowed to burn for a short time (a tree branch might burn away). Semipermanent faults occur more frequently in the
subtransmission lines and
electric distribution;
* a ''permanent fault'' must be repaired. Almost all the faults on the
underground power cable are permanent.
Many pieces of the grid equipment can develop internal problems. For these devices, the faults can be classified into ''
internal'' and ''external''. As an example of the internal fault, a transformer might develop overpressure inside it containment vessel with its root cause (for example, local overheating) not triggering any other alarms. For the same transformer, an overload condition would represent an external fault.
Relay types

The relays can be classified by their sensitivity to the location of a fault:
* a ''nondirectional'' relay does not provide an information on which side of it the fault is located, this is the simplest form of the
overcurrent relay. For example, in a
radial system of
electrical power distribution
Electric power distribution is the final stage in the delivery of electricity. Electricity is carried from the transmission system to individual consumers. Distribution substations connect to the transmission system and lower the transmission ...
, the current always flow to the load spokes, so there is not need to sense its direction, as an overcurrent condition always indicates a short circuit on the load side;
* a
directional relay compares the current phase with the reference and performs action only if the direction to the fault matches the selected one;
* a
differential relay compares the values of electrical measurements on the input and output of a protected device. For example, in an
electrical transformer, input and output voltage and current values are related through the
transformer ratio, and large deviations from this constant indicate a fault;
* a
distance relay determines the distance of the fault by calculating the line
electrical impedance
In electrical engineering, impedance is the opposition to alternating current presented by the combined effect of Electrical_resistance, resistance and Electrical_reactance, reactance in a electrical circuit, circuit.
Quantitatively, the impedan ...
as seen by the relay based on observe current, voltage, and the phase difference between them. The knowledge of distance can be used to prevent tripping when the fault is in the wrong zone;
* a pilot protection relay senses the conditions on the other end of the line through a communication channel (wire pilot, carrier pilot, microwave pilot, and fiber-optic pilot).
In the 21st century a lot of testing for abnormal conditions is performed by multifunctional
numerical relays that use computers for calculations. Individual measurements use cryptic identifiers from the
ANSI device numbers list, like "50" for the "Instantaneous Overcurrent Relay" or "87L" for the "Segregated Line Current Differential".
Historically, the power industry went through multiple generations of sensors and comparators, retaining the terminology and some of the devices:
* ''
electromechanical relays'' are the simplest devices used for protection since the early days of electrical power industry. For example, an
induction disk overcurrent relay is an overcurrent relay that uses an
induction disk as a sensor and timing element;
* ''electronic relays'', with
comparators and
level detectors were introduced slowly over a long period of time starting in the 1930s. The process accelerated with the arrival of
transistor
A transistor is a semiconductor device used to Electronic amplifier, amplify or electronic switch, switch electrical signals and electric power, power. It is one of the basic building blocks of modern electronics. It is composed of semicondu ...
in 1950s.
* ''
digital relays'' were proposed in 1969, but became widespread only with the introduction of
microprocessor
A microprocessor is a computer processor (computing), processor for which the data processing logic and control is included on a single integrated circuit (IC), or a small number of ICs. The microprocessor contains the arithmetic, logic, a ...
in the early 1970s.
Types of protection
High-voltage transmission network
Protection of the transmission and distribution system serves two functions: protection of the plant and protection of the public (including employees). At a basic level, protection disconnects equipment that experiences an overload or a short to earth. Some items in substations such as transformers might require additional protection based on temperature or gas pressure, among others.
Generator sets
In a power plant, the protective relays are intended to prevent damage to
alternators or to the
transformer
In electrical engineering, a transformer is a passive component that transfers electrical energy from one electrical circuit to another circuit, or multiple Electrical network, circuits. A varying current in any coil of the transformer produces ...
s in case of abnormal conditions of operation, due to internal failures, as well as insulating failures or regulation malfunctions. Such failures are unusual, so the protective relays have to operate very rarely. If a protective relay fails to detect a fault, the resulting damage to the alternator or to the transformer might require costly equipment repairs or replacement, as well as income loss from the inability to produce and sell energy.
Overload and back-up for distance (overcurrent)
Overload protection requires a current transformer which simply measures the current in a circuit and compares it to the predetermined value. There are two types of overload protection: instantaneous overcurrent (IOC) and time overcurrent (TOC). Instantaneous overcurrent requires that the current exceeds a predetermined level for the circuit breaker to operate. Time overcurrent protection operates based on a current vs time curve. Based on this curve, if the measured current exceeds a given level for the preset amount of time, the circuit breaker or fuse will operate.
Earth fault/ground fault
Earth fault protection also requires current transformers and senses an imbalance in a three-phase circuit. Normally the three phase currents are in balance, i.e. roughly equal in magnitude. If one or two phases become connected to earth via a low impedance path, their magnitudes will increase dramatically, as will current imbalance. If this imbalance exceeds a pre-determined value, a circuit breaker should operate. Restricted earth fault protection is a type of earth fault protection which looks for earth fault between two sets of current transformers (hence restricted to that zone).
Distance (impedance relay)
Distance protection detects both voltage and current. A fault on a circuit will generally create a sag in the voltage level. If the ratio of voltage to current measured at the relay terminals, which equates to an impedance, lands within a predetermined level the circuit breaker will operate. This is useful for reasonably long lines, lines longer than 10 miles, because their operating characteristics are based on the line characteristics. This means that when a fault appears on the line the impedance setting in the relay is compared to the apparent impedance of the line from the relay terminals to the fault. If the relay setting is determined to be below the apparent impedance it is determined that the fault is within the zone of protection. When the transmission line length is too short, less than 10 miles, distance protection becomes more difficult to coordinate. In these instances the best choice of protection is current differential protection.
Low-voltage networks
The
low-voltage network generally relies upon fuses or low-voltage circuit breakers to remove both overload and earth faults.
Cybersecurity
The bulk system which is a large interconnected electrical system including transmission and control system is experiencing new cybersecurity threats every day. (“Electric Grid Cybersecurity,” 2019). Most of these attacks are aiming the control systems in the grids. These control systems are connected to the internet and makes it easier for hackers to attack them. These attacks can cause damage to equipment and limit the utility professionals ability to control the system.
Coordination
Protective device coordination is the process of determining the "best fit" timing of current interruption when abnormal electrical conditions occur. The goal is to minimize an outage to the greatest extent possible. Historically, protective device coordination was done on translucent log–log paper. Modern methods normally include detailed computer based analysis and reporting.
Protection coordination is also handled through dividing the power system into protective zones. If a fault were to occur in a given zone, necessary actions will be executed to isolate that zone from the entire system. Zone definitions account for
generators, buses,
transformer
In electrical engineering, a transformer is a passive component that transfers electrical energy from one electrical circuit to another circuit, or multiple Electrical network, circuits. A varying current in any coil of the transformer produces ...
s,
transmission and distribution lines, and
motors. Additionally, zones possess the following features: zones overlap, overlap regions denote circuit breakers, and all circuit breakers in a given zone with a fault will open in order to isolate the fault. Overlapped regions are created by two sets of instrument transformers and relays for each circuit breaker. They are designed for redundancy to eliminate unprotected areas; however, overlapped regions are devised to remain as small as possible such that when a fault occurs in an overlap region and the two zones which encompass the fault are isolated, the sector of the power system which is lost from service is still small despite two zones being isolated.
Disturbance-monitoring equipment
Disturbance-monitoring equipment (DME) monitors and records system data pertaining to a
fault. DME accomplish three main purposes:
* model validation,
*disturbance investigation, and
*assessment of system protection performance.
DME devices include:
*Sequence of event recorders, which record equipment response to the event
*Fault recorders, which record actual waveform data of the system primary voltages and currents
*Dynamic disturbance recorders (DDRs), which record incidents that portray power system behavior during dynamic events such as low frequency (0.1 Hz – 3 Hz) oscillations and abnormal frequency or voltage excursions
Performance measures
Protection engineers define dependability as the tendency of the protection system to operate correctly for in-zone faults. They define security as the tendency not to operate for out-of-zone faults. Both dependability and security are reliability issues. Fault tree analysis is one tool with which a protection engineer can compare the relative reliability of proposed protection schemes. Quantifying protection reliability is important for making the best decisions on improving a protection system, managing dependability versus security tradeoffs, and getting the best results for the least money. A quantitative understanding is essential in the competitive utility industry.
*Reliability: Devices must function consistently when fault conditions occur, regardless of possibly being idle for months or years. Without this reliability, systems may cause costly damages.
*Selectivity: Devices must avoid unwarranted, false trips.
*Speed: Devices must function quickly to reduce equipment damage and fault duration, with only very precise intentional time delays.
*Sensitivity: Devices must detect even the smallest value of faults and respond.
*Economy: Devices must provide maximum protection at minimum cost.
*Simplicity: Devices must minimize protection circuitry and equipment.
Reliability: Dependability vs Security
There are two aspects of reliable operation of protection systems: dependability and security.
[NERC Reliability Fundamentals of System Protection, December 2010, Sec 3 - 4.1.2.3, https://www.nerc.com/comm/PC/System%20Protection%20and%20Control%20Subcommittee%20SPCS%20DL/Protection%20System%20Reliability%20Fundamentals_Approved_20101208.pdf] Dependability is the ability of the protection system to operate when called upon to remove a faulted element from the power system. Security is the ability of the protection system to restrain itself from operating during an external fault. Choosing the appropriate balance between security and dependability in designing the protection system requires engineering judgement and varies on a case-by-case basis.
See also
*
Fault current limiter
*
Network analyzer (AC power)
*
Prospective short-circuit current
*