HOME

TheInfoList



OR:

A heat detector is a fire alarm device designed to respond when the convected thermal energy of a fire increases the temperature of a heat sensitive element. The thermal mass and conductivity of the element regulate the rate flow of heat into the element. All heat detectors have this
thermal lag Thermal lag describes a body's temperature with respect to time as a result of its thermal mass. A body with high thermal mass (high heat capacity and low Thermal conductivity, conductivity) will have a large thermal lag. :Thermal \ lag (s) = α ...
. Heat detectors have two main classifications of operation, "rate-of-rise" and "fixed temperature". The heat detector is used to help in the reduction of property damage.


Fixed temperature heat detectors

This is the most common type of heat detector. Fixed temperature detectors operate when the heat sensitive
eutectic alloy A eutectic system or eutectic mixture ( ) is a homogeneous mixture that has a melting point lower than those of the constituents. The lowest possible melting point over all of the mixing ratios of the constituents is called the ''eutectic tem ...
reaches the eutectic point changing state from a solid to a liquid. Thermal lag delays the accumulation of heat at the sensitive element so that a fixed-temperature device will reach its
operating temperature An operating temperature is the allowable temperature range of the local ambient environment at which an electrical or mechanical device operates. The device will operate effectively within a specified temperature range which varies based on the de ...
sometime after the surrounding air temperature exceeds that temperature. The most common fixed temperature point for electrically connected heat detectors is 58°C (136.4°F).


Rate-of-rise heat detectors

Rate-of-Rise (ROR) heat detectors operate on a rapid rise in element temperature of 6.7° to 8.3°C (12° to 15°F) increase per minute, irrespective of the starting temperature. This type of heat detector can operate at a lower temperature fire condition than would be possible if the threshold were fixed. It has two heat-sensitive thermocouples or thermistors. One thermocouple monitors heat transferred by convection or radiation while the other responds to ambient temperature. The detector responds when the first sensing element's temperature increases relative to the other. Rate of rise detectors may not respond to low energy release rates of slowly developing fires. To detect slowly developing fires combination detectors add a fixed temperature element that will ultimately respond when the fixed temperature element reaches the design threshold.


Heat detector selection

Heat detectors commonly have a label on them that reads "Not a life safety device". That is because heat detectors are not meant to replace smoke detectors in the bedrooms or in the hallway outside of the bedrooms. A heat detector will nonetheless notify of a fire in a kitchen or utility area, ''e.g.'', laundry room, garage, or attic, where smoke detectors should not be installed as dust or other particles would affect the smoke detector and cause false alarms. This will allow extra time to evacuate the building or to put out the fire, if possible. Mechanical heat detectors are independent fire warning stations that — unlike smoke detectors — can be installed in any area of a home. Portability, ease of installation, and excellent performance and reliability make this a good choice for residential fire protection when combined with the required smoke detectors. Because the detectors are not interconnected, heat activation identifies the location of the fire, facilitating evacuation from the home. Each type of heat detector has its advantages, and it cannot be said that one type of heat detector should always be used instead of another. If one were to place a rate-of-rise heat detector above a large, closed oven, then every time the door is opened a nuisance alarm could be generated due to the sudden heat transient. In this circumstance the fixed threshold detector would probably be best. If a room filled with highly combustible materials is protected with a fixed heat detector, then a fast-flaming fire could exceed the alarm threshold due to
thermal lag Thermal lag describes a body's temperature with respect to time as a result of its thermal mass. A body with high thermal mass (high heat capacity and low Thermal conductivity, conductivity) will have a large thermal lag. :Thermal \ lag (s) = α ...
. In that case the rate-of-rise heat detector may be preferred.


See also

* Aspirating smoke detector * Automatic fire suppression * Carbon monoxide detector *
Fire alarm system A fire alarm system warns people when smoke, fire, carbon monoxide or other fire-related or general notification emergency, emergencies are detected. These alarms may be activated automatically from smoke detectors and heat detectors or may also ...
* Fire sprinkler * Flame detector * Gaseous fire suppression * Manual fire alarm activation *
Passive infrared sensor A passive infrared sensor (PIR sensor) is an electronic sensor that measures infrared (IR) light radiating from objects in its field of view. They are most often used in PIR-based motion detectors. PIR sensors are commonly used in security alarms ...
* Smoke detector {{DEFAULTSORT:Heat Detector Active fire protection Safety equipment Fire detection and alarm Firefighting equipment Detectors ja:自動火災報知設備#感知器