Uses
Duct leakage testers are used in residential single family, residential multi-family, and commercial buildings that have a forced air delivery systems for heating and cooling.Operation
A basic duct leakage testing system includes three components: a calibrated fan, a register sealing system, and a device to measure fan flow and building pressure. Supply registers or return air grills are sealed using adhesive tapes, cardboard, or non-adhesive reusable seals. One register or return is left unsealed, and the calibrated fan is connected to it. Pressure is monitored in one of the branches of the ductwork while the calibrated fan delivers air into the system. As air is delivered into the ductwork, pressure builds and forces air out of all of the openings in the various ductwork connections or through the seams and joints of the furnace or air-conditioner. The tighter the ductwork system (e.g. fewer holes), the less air is needed from the fan to create a change in the ductwork pressure. A duct leakage test can be performed by either pressurizing or depressurizing the ductwork. Ductwork that is outside the building envelope, such as in an unconditioned attic or crawlspace, should be pressurized so as to not bring in unwanted contaminants such as dust.Measurements
Duct tester airtightness measurements are presented in a number of different formats including but not limited to:Air flow (CFM)
CFM25 is defined as the air flow (in cubic feet per minute) needed to create a 25 Pascal pressure change in the ductwork. CFM25 is one of the most basic measurements of ductwork airtightness. A pressure of 25 Pa is equal to 0.1 inches (0.25 cm) of water column.Leakage area
Leakage area estimates are a useful way to visualize the equivalent cumulative size of all leaks or holes in the ductwork. There are a variety of standard calculation methods used to estimate leakage areas.Ratings
Commercial and industrial ductwork is often tested to standards developed by the Sheet Metal and Air Conditioning Contractors' National Association (SMACNA). Ductwork is temporarily subjected to higher pressures, and then given a rating or classification rather than a leakage estimate.Additional methods
Leakage to outside
The above test procedure describes how to determine total duct leakage, or how much leakage there is for all of the ductwork connected to the HVAC system. Another test is for duct leakage to the outside. Depending on the location of the house in the United States, some HVAC systems are completely inside the thermal envelope, some are completely outside the thermal envelope, and some are a combination of the two. Energy conservation is improved mostly by sealing ductwork that is outside the thermal envelope or connected to the outside. With mixed systems, it is possible to determine amount of leakage to the outside by simultaneously pressurizing the house while pressurizing the ductwork, and measuring the amount of flow that is required to equalize the pressure.Blower door subtraction
Another form of duct leakage to outside uses aPressure pan test
References