Coupling Capacitor Potential Device
   HOME

TheInfoList



OR:

Voltage transformers (VT), also called potential transformers (PT), are a parallel-connected type of
instrument transformer Instrument transformers are high accuracy class electrical devices used to isolate or transform voltage or current levels. The most common usage of instrument transformers is to operate instruments or metering from high voltage or high current circu ...
. They are designed to present a negligible load to the supply being measured and have an accurate voltage ratio and phase relationship to enable accurate secondary connected metering.


Ratio

The PT is typically described by its voltage ratio from primary to secondary. A 600:120 PT will provide an output voltage of 120 volts when 600 volts are impressed across its primary winding. Standard secondary voltage ratings are 120 volts and 70 volts, compatible with standard measuring instruments.


Burden and accuracy

Burden and accuracy are usually stated as a combined parameter due to being dependent on each other. Metering style PTs are designed with smaller cores and VA capacities than power transformers. This causes metering PTs to saturate at lower secondary voltage outputs saving sensitive connected metering devices from damaging large voltage spikes found in grid disturbances. A small PT (see nameplate in photo) with a rating of 0.3W, 0.6X would indicate with up to W load (12.5 watts) of secondary burden the secondary current will be within a 0.3 percent error parallelogram on an accuracy diagram incorporating both phase angle and ratio errors. The same technique applies for the X load (25 watts) rating except inside a 0.6% accuracy parallelogram.


Markings

Transformer winding primary (usually high-voltage) connecting wires are of many types. They may be labeled as H1, H2 (sometimes H0 if it is internally designed to be grounded) and X1, X2 and sometimes an X3 tap may be present. Sometimes a second isolated winding (Y1, Y2, Y3) (and third (Z1, Z2, Z3) may also be available on the same voltage transformer. The primary may be connected phase to ground or phase to phase. The secondary is usually grounded on one terminal to avoid capacitive induction from damaging low-voltage equipment and for human safety.


Types of voltage transformers

There are three primary types of potential transformers (PT): electromagnetic, capacitor, and optical. *An electromagnetic potential transformer is a wire-wound transformer. *An optical voltage transformer exploits the
Faraday effect The Faraday effect or Faraday rotation, sometimes referred to as the magneto-optic Faraday effect (MOFE), is a physical magneto-optical phenomenon. The Faraday effect causes a polarization rotation which is proportional to the projection of the ...
, rotating polarized light, in optical materials. *A capacitor voltage transformer, or capacitive voltage transformer uses a capacitive
voltage divider In electronics, a voltage divider (also known as a potential divider) is a passive linear circuit that produces an output voltage (''V''out) that is a fraction of its input voltage (''V''in). Voltage division is the result of distributing the i ...
to reduce the line voltage before applying it to an ordinary electromagnetic transformer.


capacitor voltage transformer

A capacitor voltage transformer (CVT), is a
transformer In electrical engineering, a transformer is a passive component that transfers electrical energy from one electrical circuit to another circuit, or multiple Electrical network, circuits. A varying current in any coil of the transformer produces ...
used in
power systems IBM Power Systems is a family of server computers from IBM that are based on its Power processors. It was created in 2008 as a merger of the System p and System i product lines. History IBM had two distinct POWER- and PowerPC-based hardwar ...
to step down
extra high voltage High voltage electricity refers to electrical potential large enough to cause injury or damage. In certain industries, ''high voltage'' refers to voltage above a certain threshold. Equipment and conductors that carry high voltage warrant spec ...
signals and provide a
low voltage In electrical engineering, low voltage is a relative term, the definition varying by context. Different definitions are used in electric power transmission and distribution, compared with electronics design. Electrical safety codes define "low vo ...
signal to the actual VT (voltage transformer) used for operating metering/protective relays due to a lower cost than an electromagnetic PT. In its most basic form, the device consists of three parts: a two
capacitor In electrical engineering, a capacitor is a device that stores electrical energy by accumulating electric charges on two closely spaced surfaces that are insulated from each other. The capacitor was originally known as the condenser, a term st ...
voltage divider In electronics, a voltage divider (also known as a potential divider) is a passive linear circuit that produces an output voltage (''V''out) that is a fraction of its input voltage (''V''in). Voltage division is the result of distributing the i ...
across which the transmission line, an inductive element to tune the device to the line frequency, and a voltage transformer to isolate and further step down the voltage for metering devices or protective relay. The tuning of the divider to the line frequency makes the overall division ratio less sensitive to changes in the burden of the connected metering or protection devices. The device has at least four terminals: a terminal for connection to the high voltage signal, a ground terminal, and two secondary terminals which connect to the instrumentation or protective relay. Capacitor C1 is often constructed as a stack of smaller capacitors connected in series. This provides a large voltage drop across C1 and a relatively small voltage drop across C2. As the majority of the voltage drop is on C1, this reduces the required insulation level of the voltage transformer. This makes CVTs more economical than the wound voltage transformers under high voltage (over 100kV), as the latter one requires more winding and materials. In communication systems, CVTs in combination with wave traps are used for filtering high-frequency communication signals from power frequency.Stanley H. Horowitz, Arun G. Phadke ''Power system relaying third edition'', John Wiley and Sons, 2008 pages 64–65 This forms a carrier communication network throughout the transmission network, to communicate between substations.


References

{{Electric transformers Electric transformers