A contactor is an electrically controlled switch used for switching an electrical power circuit. A contactor is typically controlled by a circuit which has a much lower power level than the switched circuit, such as a 24-volt coil electromagnet controlling a 230-volt motor switch. Unlike general-purpose
relay A relay Electromechanical relay schematic showing a control coil, four pairs of normally open and one pair of normally closed contacts An automotive-style miniature relay with the dust cover taken off A relay is an electrically operated switc ...
s, contactors are designed to be directly connected to high-current load devices. Relays tend to be of lower capacity and are usually designed for both ''normally closed'' and ''normally open'' applications. Devices switching more than 15 amperes or in circuits rated more than a few kilowatts are usually called contactors. Apart from optional auxiliary low-current contacts, contactors are almost exclusively fitted with normally open ("form A") contacts. Unlike relays, contactors are designed with features to control and suppress the arc produced when interrupting heavy motor currents. Unlike a
circuit breaker A circuit breaker is an electrical safety device designed to protect an Electrical network, electrical circuit from damage caused by current in excess of that which the equipment can safely carry (overcurrent). Its basic function is to interr ...
, a contactor is not intended to interrupt a
short circuit A short circuit (sometimes abbreviated to short or s/c) is an electrical circuit that allows a current to travel along an unintended path with no or very low electrical impedance. This results in an excessive current flowing through the circuit ...
current. Contactors range from those having a breaking current of several amperes to thousands of amperes and 24 V DC to many kilovolts. The physical size of contactors ranges from a device small enough to pick up with one hand, to large devices approximately a meter (yard) on a side. Contactors are used to control
electric motor An electric motor is a machine that converts electrical energy into mechanical energy. Most electric motors operate through the interaction between the motor's magnetic field and electric current in a electromagnetic coil, wire winding to gene ...
s,
lighting Lighting or illumination is the deliberate use of light to achieve practical or aesthetic effects. Lighting includes the use of both artificial light sources like lamps and light fixtures, as well as natural illumination by capturing daylight. ...
, heating,
capacitor In electrical engineering, a capacitor is a device that stores electrical energy by accumulating electric charges on two closely spaced surfaces that are insulated from each other. The capacitor was originally known as the condenser, a term st ...
banks, thermal evaporators, and other electrical loads.


Construction

A contactor has three components: * The ''contacts'' are the current-carrying part of the contactor. This includes power contacts, auxiliary contacts, and contact springs. Contact material is chosen for high electrical conductivity, mechanical strength, and stability under arcing and oxidation. Commonly used metals include alloys of tungsten, molybdenum, copper, and others. For example, motor circuit contactors may use contacts made of silver with cadmium oxide added to improved durability and arc resistance. * The ''electromagnet'' (or "''coil''") provides the driving force to close the contacts. The ''enclosure'' is a frame housing the contacts and the electromagnet. Enclosures are made of insulating materials such as
Bakelite Bakelite ( ), formally , is a thermosetting polymer, thermosetting phenol formaldehyde resin, formed from a condensation reaction of phenol with formaldehyde. The first plastic made from synthetic components, it was developed by Belgian chemist ...
, Nylon 6, and thermosetting plastics to protect and insulate the contacts and to provide some measure of protection against personnel touching the contacts. Open-frame contactors may have a further enclosure to protect against dust, oil, explosion hazards and weather. * s use blowout coils to lengthen and move the
electric arc An electric arc (or arc discharge) is an electrical breakdown of a gas that produces a prolonged electrical discharge. The electric current, current through a normally Electrical conductance, nonconductive medium such as air produces a plasma ( ...
. These are especially useful in DC power circuits. AC arcs have periods of low current, during which the arc can be extinguished with relative ease, but DC arcs have continuous high current, so blowing them out requires the arc to be stretched further than an AC arc of the same current. The magnetic blowouts in the pictured Albright contactor (which is designed for DC currents) more than double the current the contactor can break, increasing it from 600 A to 1,500 A. Sometimes an economizer circuit is also installed to reduce the power required to keep a contactor closed; an auxiliary contact reduces coil current after the contactor closes. A somewhat greater amount of power is required to initially close a contactor than is required to keep it closed. Such a circuit can save a substantial amount of power and allow the energized coil to stay cooler. Economizer circuits are nearly always applied on direct-current contactor coils and on large alternating current contactor coils. A basic contactor will have a coil input (which may be driven by either an AC or DC supply depending on the contactor design). Universal coils (driven by AC as well as DC) are also available in the market today. The coil may be energized at the same voltage as a motor the contactor is controlling, or may be separately controlled with a lower coil voltage better suited to control by programmable controllers and lower-voltage pilot devices. Certain contactors have series coils connected in the motor circuit; these are used, for example, for automatic acceleration control, where the next stage of resistance is not cut out until the motor current has dropped.


Operating principle

When current passes through the
electromagnet An electromagnet is a type of magnet in which the magnetic field is produced by an electric current. Electromagnets usually consist of wire (likely copper) wound into a electromagnetic coil, coil. A current through the wire creates a magnetic ...
, a magnetic field is produced, which attracts the moving core of the contactor. The electromagnet coil draws more current initially, until its
inductance Inductance is the tendency of an electrical conductor to oppose a change in the electric current flowing through it. The electric current produces a magnetic field around the conductor. The magnetic field strength depends on the magnitude of the ...
increases when the metal core enters the coil. The moving contact is propelled by the moving core; the force developed by the electromagnet holds the moving and fixed contacts together. When the contactor coil is de-energized, gravity or a spring returns the electromagnet core to its initial position and opens the contacts. For contactors energized with
alternating current Alternating current (AC) is an electric current that periodically reverses direction and changes its magnitude continuously with time, in contrast to direct current (DC), which flows only in one direction. Alternating current is the form in w ...
, a small part of the core is surrounded with a shading coil, which slightly delays the magnetic flux in the core. The effect is to average out the alternating pull of the magnetic field and so prevent the core from buzzing at twice line frequency. Because arcing and consequent damage occurs just as the contacts are opening or closing, contactors are designed to open and close very rapidly; there is often an internal tipping point mechanism to ensure rapid action. Rapid closing can, however, lead to increase contact bounce which causes additional unwanted open-close cycles. One solution is to have bifurcated contacts to minimize contact bounce; two contacts designed to close simultaneously, but bounce at different times so the circuit will not be briefly disconnected and cause an arc. Another technique for improving the life of contactors is contact wipe; the contacts move past each other after initial contact in order to wipe off any contamination.


Arc suppression

Without adequate contact protection, the occurrence of electric current arcing causes significant degradation of the contacts, which suffer significant damage. An electrical arc occurs between the two contact points (electrodes) when they transition from a closed to an open (break arc) or from an open to a closed (make arc). The break arc is typically more energetic and thus more destructive. The heat developed by the resulting electrical arc is very high, ultimately causing the metal on the contact to migrate with the current. The extremely high temperature of the arc (tens of thousands of degrees Celsius) cracks the surrounding gas molecules creating
ozone Ozone () (or trioxygen) is an Inorganic compound, inorganic molecule with the chemical formula . It is a pale blue gas with a distinctively pungent smell. It is an allotrope of oxygen that is much less stable than the diatomic allotrope , break ...
,
carbon monoxide Carbon monoxide (chemical formula CO) is a poisonous, flammable gas that is colorless, odorless, tasteless, and slightly less dense than air. Carbon monoxide consists of one carbon atom and one oxygen atom connected by a triple bond. It is the si ...
, and other compounds. The arc energy slowly destroys the contact metal, causing some material to escape into the air as fine particulate matter. This activity causes the material in the contacts to degrade over time, ultimately resulting in device failure. For example, a properly applied contactor will have a life span of 10,000 to 100,000 operations when run under power; which is significantly less than the mechanical (non-powered) life of the same device which can be in excess of 20 million operations. Most motor control contactors at low voltages (600 volts and less) are air break contactors; air at atmospheric pressure surrounds the contacts and extinguishes the arc when interrupting the circuit. Modern medium-voltage AC motor controllers use vacuum contactors. High voltage AC contactors (greater than 1,000 volts) may use vacuum or an inert gas around the contacts. High voltage DC contactors (greater than 600 V) still rely on air within specially designed arc-chutes to break the arc energy. High-voltage electric locomotives may be isolated from their overhead supply by roof-mounted circuit breakers actuated by compressed air; the same air supply may be used to "blow out" any arc that forms.


Ratings

Contactors are rated by designed load current per contact (pole), maximum fault withstand current, duty cycle, design life expectancy, voltage, and coil voltage. A general purpose motor control contactor may be suitable for heavy starting duty on large motors; so-called "definite purpose" contactors are carefully adapted to such applications as air-conditioning compressor motor starting. North American and European ratings for contactors follow different philosophies, with North American general purpose machine tool contactors generally emphasizing simplicity of application while definite purpose and European rating philosophy emphasizes design for the intended life cycle of the application.


IEC utilization categories

The current rating of the contactor depends on utilization category. Example IEC categories in standard 60947 are described as: * AC-1 – Non-inductive or slightly inductive loads, resistance furnaces * AC-2 – Starting of slip-ring motors: starting, switching-off * AC-3 – Starting of squirrel-cage motors and switching-off only after the motor is up to speed. (Make Locked Rotor Amps (LRA), Break Full Load Amps (FLA)) * AC-4 – Starting of squirrel-cage motors with inching and plugging duty. Rapid Start/Stop. (Make and Break LRA) Relays and auxiliary contact blocks are rated according to IEC 60947-5-1: * AC-15 – Control of electromagnetic loads (>72 VA) * DC-13 – Control of electromagnets


NEMA

NEMA The National Electrical Manufacturers Association (NEMA) is the largest trade association of electrical equipment manufacturers in the United States. Founded in 1926, it advocates for the industry and publishes standards for electrical product ...
contactors for low-voltage motors (less than 1,000 volts) are rated according to NEMA size, which gives a maximum continuous current rating and a rating by horsepower for attached induction motors. NEMA standard contactor sizes are designated 00, 0, 1, 2, 3 to 9. The horsepower ratings are based on voltage and on typical induction motor characteristics and
duty cycle A duty cycle or power cycle is the fraction of one period in which a signal or system is active. Duty cycle is commonly expressed as a percentage or a ratio. A period is the time it takes for a signal to complete an on-and-off cycle. As a for ...
as stated in NEMA standard ICS2. Exceptional duty cycles or specialized motor types may require a different NEMA starter size than the nominal rating. Manufacturer's literature is used to guide selection for non-motor loads, for example, incandescent lighting or power factor correction capacitors. Contactors for medium-voltage motors (greater than 1,000 volts) are rated by voltage and current capacity. Auxiliary contacts of contactors are used in control circuits and are rated with
NEMA contact ratings NEMA contact ratings are how much current at a rated voltage a relay or other pilot device can switch. The current rating of smaller NEMA The National Electrical Manufacturers Association (NEMA) is the largest trade association of electrical ...
for the pilot circuit duty required. Normally these contacts are not used in motor circuits. The nomenclature is a letter followed by a three-digit number, the letter designates the current rating of the contacts and the current type (i.e., AC or DC) and the number designates the maximum voltage design values.


Applications


Lighting control

Contactors are often used to provide central control of large lighting installations, such as an office building or retail building. To reduce power consumption in the contactor coils, latching contactors are used, which have two operating coils. One coil, momentarily energized, closes the power circuit contacts, which are then mechanically held closed; the second coil opens the contacts.


Magnetic starter

A magnetic starter is a device designed to provide power to electric motors. It includes a contactor as an essential component, while also providing power-cutoff, under-voltage, and overload protection.


Vacuum contactor

Vacuum contactors utilize vacuum bottle encapsulated contacts to suppress the arc. This arc suppression allows the contacts to be much smaller and use less space than air break contacts at higher currents. As the contacts are encapsulated, vacuum contactors are used fairly extensively in dirty applications, such as mining. Vacuum contactors are also widely used at medium voltages from 1000 to 5000 volts, effectively displacing oil-filled circuit breakers in many applications. Vacuum contactors are only applicable for use in AC systems. The AC arc generated upon opening of the contacts will self-extinguish at the zero-crossing of the current waveform, with the vacuum preventing a re-strike of the arc across the open contacts. Vacuum contactors are therefore very efficient at disrupting the energy of an electric arc and are used when relatively fast switching is required, as the maximum break time is determined by the periodicity of the AC waveform. In the case of 60 Hz power (North American standard), the power will discontinue within 1/120 of a second (8.3ms).


Mercury relay

A
mercury relay A mercury relay (mercury displacement relay, mercury contactor) is a relay that uses mercury as the switching element. They are used as high-current switches or contactors, where contact erosion from constant cycling would be a problem for conv ...
, sometimes called a mercury displacement relay, or, mercury contactor, is a relay that uses the liquid metal mercury in an insulated sealed container as the switching element.


Mercury-wetted relay

A mercury-wetted relay is a form of relay, usually a reed relay, in which the contacts are wetted with mercury. These are not considered contactors because they are not intended for currents above 15 amps.


Camshaft operation

When a series of contactors is to be operated in sequence, this may be done by a
camshaft A camshaft is a shaft that contains a row of pointed cams in order to convert rotational motion to reciprocating motion. Camshafts are used in piston engines (to operate the intake and exhaust valves), mechanically controlled ignition syst ...
instead of by individual electromagnets. The camshaft may be driven by an electric motor or a pneumatic cylinder. Before the advent of
solid-state electronics Solid-state electronics are semiconductor electronics: electronic equipment that use semiconductor devices such as transistors, diodes and integrated circuits (ICs). The term is also used as an adjective for devices in which semiconductor elec ...
, the camshaft system was commonly used for speed control in
electric locomotive An electric locomotive is a locomotive powered by electricity from overhead lines, a third rail or on-board energy storage such as a Battery (electricity), battery or a supercapacitor. Locomotives with on-board fuelled prime mover (locomotive), ...
s.


Differences between a relay and a contactor

In addition to their current ratings and rating for motor circuit control, contactors often have other construction details not found in relays. Unlike lower-powered relays, contactors generally have special structures for arc-suppression to allow them to interrupt heavy currents, such as motor starting inrush current. Contactors usually have provision for installation of additional contact blocks, rated for pilot duty, used in motor control circuits. * It is rare to see high coil voltages for relays but often found with contactors with coil voltages from 24 V AC/DC all the way up to 600 V AC possible. * Relays often have normally closed contacts; contactors usually do not (when de-energized, there is no connection). * Combination motor starters only use contactors.


References