Gaseous fire suppression
   HOME

TheInfoList



OR:

Gaseous fire suppression, also called clean agent fire suppression, is a term to describe the use of
inert gas An inert gas is a gas that does not readily undergo chemical reactions with other chemical substances and therefore does not readily form chemical compounds. The noble gases often do not react with many substances and were historically referred to ...
es and chemical agents to extinguish a
fire Fire is the rapid oxidation of a material (the fuel) in the exothermic chemical process of combustion, releasing heat, light, and various reaction products. At a certain point in the combustion reaction, called the ignition point, flames ...
. These agents are governed by the
National Fire Protection Association The National Fire Protection Association (NFPA) is an international nonprofit organization devoted to eliminating death, injury, property and economic loss due to fire, electrical and related hazards. As of 2018, the NFPA claims to have 50,000 mem ...
(NFPA) Standard for Clean Agent Fire Extinguishing Systems – NFPA 2001 in the US, with different standards and regulations elsewhere. The system typically consists of the agent, agent storage containers, agent release valves, fire detectors, fire detection system (wiring control panel, actuation signaling), agent delivery piping, and agent dispersion nozzles.


Theory

There are four means used by the agents to extinguish a fire. They act on the "
fire tetrahedron The fire triangle or combustion triangle is a simple model for understanding the necessary ingredients for most fires. The triangle illustrates the three elements a fire needs to ignite: heat, fuel, and an oxidizing agent (usually oxygen). A ...
": * Reduction or isolation of fuel. No agents currently use this as the primary means of fire suppression. * Reduction of heat. Representative agents: Clean agent FS 49 C2 (NAF S 227, MH227, FM-200), Novec 1230,
pentafluoroethane Pentafluoroethane is a fluorocarbon with the formula CF3CHF2. Pentafluoroethane is currently used as a refrigerant (known as R-125) and also used as a fire suppression agent in fire suppression systems. Pentafluoroethane does not deplete ozone ...
(NAF S125, ECARO-25). * Reduction or isolation of oxygen: Representative agents: Argonite / IG-55 (ProInert),
carbon dioxide Carbon dioxide ( chemical formula ) is a chemical compound made up of molecules that each have one carbon atom covalently double bonded to two oxygen atoms. It is found in the gas state at room temperature. In the air, carbon dioxide is t ...
, Inert Gas 541 IG-541 Inergen, and IG-100 (NN100). * Inhibiting the chain reaction of the above components. Representative agents: FE-13, 1,1,1,2,3,3,3-Heptafluoropropane, FE-25,
haloalkane The haloalkanes (also known as halogenoalkanes or alkyl halides) are alkanes containing one or more halogen substituents. They are a subset of the general class of halocarbons, although the distinction is not often made. Haloalkanes are widely u ...
s,
bromotrifluoromethane Bromotrifluoromethane, commonly known as Halon 1301, R13B1, Halon 13B1 or BTM, is an organic halide with the chemical formula C Br F3. It is used for gaseous fire suppression as a far less toxic alternative to bromochloromethane. Table of phys ...
,
trifluoroiodomethane Trifluoroiodomethane, also referred to as trifluoromethyl iodide is a halomethane with the formula CF3I. It is an experimental alternative to Halon 1301 (CBrF3) in unoccupied areas. It would be used as a gaseous fire suppression flooding agent ...
, NAF P-IV, NAF S-III, NAF S 125, NAF S 227, and Triodide (
Trifluoroiodomethane Trifluoroiodomethane, also referred to as trifluoromethyl iodide is a halomethane with the formula CF3I. It is an experimental alternative to Halon 1301 (CBrF3) in unoccupied areas. It would be used as a gaseous fire suppression flooding agent ...
).


Application

Broadly speaking, there are two methods for applying an extinguishing agent: total flooding and local application: * Systems working on a total flooding principle apply an extinguishing agent to a three dimensional enclosed space in order to achieve a concentration of the agent (volume percent of the agent in air) adequate to extinguish the fire. These types of systems may be operated automatically by detection and related controls or manually by the operation of a system actuator. *Systems working on a local application principle apply an extinguishing agent directly onto a fire (usually a two dimensional area), or into the three dimensional region immediately surrounding the substance or object on fire. The main difference in local application from total flooding design is the absence of physical barriers enclosing the fire space. In the context of automatic extinguishing systems, local application generally refers to the use of systems that have been emplaced some time prior to their usage rather than the use of manually operated wheeled or portable fire extinguishers, although the nature of the agent delivery is similar and many automatic systems may also be activated manually. The lines are blurred somewhat with portable automatic extinguishing systems, although these are not common.


Safety precautions


Room Integrity Testing

Room Integrity Testing (RIT) is also required in conjunction with gas fire suppression systems. RIT ensures that in the event of a fire, the room's containment is sufficient to ensure the effectiveness of the suppression system. RIT works by creating pressure within the room or enclosure where the suppression system has been installed and ensuring that the gas does not escape from the room so quickly that it is unable to extinguish the fire.


Suffocation

An extinguishing system which is primarily based on inert gases, such as or nitrogen, in enclosed spaces presents a risk of suffocation. Some incidents have occurred where individuals in these spaces have been killed by inert gas release. When installed according to fire codes the systems have an excellent safety record. To prevent such occurrences, additional life safety systems are typically installed with a warning alarm that precedes the agent release. The warning, usually an audible and visible alert, advises the immediate evacuation of the enclosed space. After a preset time, the agent starts to discharge. This can be paused by activating an abort switch, which pauses the countdown as long as it is activated, allowing everyone to evacuate the area. Accidents have also occurred during maintenance of these systems, so proper safety precautions must be taken beforehand. The positive pressure and / or negative caused by these gases may be sufficient to break windows and walls. Over / Under pressure vents are mandatory on Inert gases and may be required on synthetic agents. These are installed working on the physical strength of the protected space and vary in size.


Accidents

A study carried out by the Italian Workers’ Compensation Authority and the Italian Fire Brigade (Piccolo et al., 2018) reported 12 different accidents caused by inert gas fire suppression systems that in many cases have resulted in serious injuries. From the cases analyzed, it was determined that the over pressure of inert gas systems can constitute a risk even in the presence of a system designed and built according to technical standards. On September 20, 2018, two people died after an inert gas leak from a fire suppression system located in the State Archives in Arezzo (Italy). On 8 July 2013 an explosion of Argonite cylinders tore through a Hertfordshire (U.K.) construction site, killing a plumber and injuring six other workers. Red Bee Media operates a broadcast playout facility in London, England, that is used by
BBC Television BBC Television is a service of the BBC. The corporation has operated a public broadcast television service in the United Kingdom, under the terms of a royal charter, since 1927. It produced television programmes from its own studios from 193 ...
,
Channel 4 Channel 4 is a British free-to-air public broadcast television network operated by the state-owned Channel Four Television Corporation. It began its transmission on 2 November 1982 and was established to provide a fourth television service ...
, Channel 5 and
ViacomCBS Paramount Global (doing business as Paramount) is an American multinational mass media and entertainment conglomerate owned and operated by National Amusements (79.4%) and headquartered at One Astor Plaza in Midtown Manhattan, New York. It ...
. The broadcasters upload programs and continuity links to Red Bee's servers and these are assembled into real-time feeds for transmission (broadcast or internet). On 25 September 2021 a gaseous fire suppression system at the facility was triggered, causing loss of service. It was found that an acoustic shock wave from the gas release nozzles had severely damaged the servers.


See also

*
Fire protection Fire protection is the study and practice of mitigating the unwanted effects of potentially destructive fires. It involves the study of the behaviour, compartmentalisation, suppression and investigation of fire and its related emergencies, as we ...
*
Hypoxic air technology for fire prevention Hypoxic air technology for fire prevention, also known as oxygen reduction system (ORS), is an active fire protection technique based on a permanent reduction of the oxygen concentration in the protected rooms. Unlike traditional fire suppression ...


References


External links


Fire Suppression Systems Association

National Fire Protection Association

EPA U.S. Environmental Protection Agency
{{fire fighting Active fire protection Fire suppression Firefighting equipment Industrial gases