Room air distribution is characterizing how
air The atmosphere of Earth is the layer of gases, known collectively as air, retained by Earth's gravity that surrounds the planet and forms its planetary atmosphere. The atmosphere of Earth protects life on Earth by creating pressure allowing f ...
is introduced to, flows through, and is removed from spaces.
HVAC Heating, ventilation, and air conditioning (HVAC) is the use of various technologies to control the temperature, humidity, and purity of the air in an enclosed space. Its goal is to provide thermal comfort and acceptable indoor air quality. ...
airflow in spaces generally can be classified by two different types: ''mixing'' (or dilution) and ''displacement''.


Mixing systems

Mixing systems generally supply air such that the supply air mixes with the room air so that the mixed air is at the room design temperature and humidity. In cooling mode, the cool supply air, typically around 55 °F (13 °C) (saturated) at design conditions, exits an outlet at high velocity. The high-velocity supply air stream causes turbulence causing the room air to mix with the supply air. Because the entire room is near-fully mixed, temperature variations are small while the contaminant concentration is fairly uniform throughout the entire room. Diffusers are normally used as the air outlets to create the high-velocity supply air stream. Most often, the air outlets and inlets are placed in the ceiling. Supply diffusers in the ceiling are fed by
fan coil unit A fan coil unit (FCU), also known as a Vertical Fan Coil-Unit (VFC), is a device consisting of a heat exchanger (coil) and a fan. As part of an HVAC system found in residential, commercial, and industrial buildings using ducted split air condi ...
s in the ceiling void or by air handling units in a remote plant room. The fan coil or handling unit takes in return air from the ceiling void and mix this with fresh air and cool, or heat it, as required to achieve the room design conditions. This arrangement is known as 'conventional room air distribution'.''Designer's Guide to Ceiling-Based Room Air Diffusion'', Rock and Zhu,
ASHRAE The American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE ) is an American professional association seeking to advance heating, ventilation, air conditioning and refrigeration (HVAC&R) systems design and constructi ...
, Inc., Atlanta, GA, USA, 2002


Outlet types

*Group A1: In or near the ceiling that discharge air horizontallyASHRAE Handbook: Fundamentals, 2021 *Group A2: Discharging horizontally that are not influenced by an adjacent surface *Group B: In or near the floor that discharge air vertically in a linear jet *Group C: In or near the floor that discharge air vertically in a spreading jet *Group D: In or near the floor that discharge air horizontally *Group E: Project supply air vertically downward


Displacement ventilation

Displacement ventilation systems supply air directly to the occupied zone. The air is supplied at low velocities to cause minimal induction and mixing. This system is used for ventilation and cooling of large high spaces, such as auditorium and atria, where energy may be saved if only the occupied zone is treated rather than trying to control the conditions in the entire space. Displacement room airflow presents an opportunity to improve both the
thermal comfort Thermal comfort is the condition of mind that expresses satisfaction with the thermal environment and is assessed by subjective evaluation ( ANSI/ASHRAE Standard 55).ANSI/ASHRAE Standard 55-2017, Thermal Environmental Conditions for Human Occupan ...
and
indoor air quality Indoor air quality (IAQ) is the air quality within and around buildings and structures. IAQ is known to affect the health, comfort, and well-being of building occupants. Poor indoor air quality has been linked to sick building syndrome, reduce ...
(IAQ) of the occupied space. It also takes advantage of the difference in air density between an upper contaminated zone and a lower clean zone. Cool air is supplied at low velocity into the lower zone. Convection from heat sources creates vertical air motion into the upper zone where high-level return inlets extract the air. In most cases these convection heat sources are also the contamination sources (e.g., people, equipment, or processes), thereby carrying the contaminants up to the upper zone, away from the occupants. The displacement outlets are usually located at or near the floor with the air supply designed so the air flows smoothly across the floor. Where there is a heat source (such as people, lighting, computers, electrical equipment, etc.) the air will rise, pulling the cool supply air up with it and moving contaminants and heat from the occupied zone to the return or exhaust grilles above. By doing so, the air quality in the occupied zone is generally superior to that achieved with mixing room air distribution. Since the conditioned air is supplied directly into the occupied space, supply air temperatures must be higher than mixing systems (usually above 63 °F or 17 °C) to avoid cold draughts at the floor. By introducing the air at supply air temperatures close to the room temperature and low outlet velocity a high level of thermal comfort can be provided with displacement ventilation.


See also

*
Dilution (equation) Dilution is the process of decreasing the concentration of a solute in a solution, usually simply by mixing with more solvent like adding more water to the solution. To dilute a solution means to add more solvent without the addition of more sol ...
* Duct (HVAC) *
HVAC Heating, ventilation, and air conditioning (HVAC) is the use of various technologies to control the temperature, humidity, and purity of the air in an enclosed space. Its goal is to provide thermal comfort and acceptable indoor air quality. ...
*
Underfloor air distribution Underfloor air distribution (UFAD) is an air distribution strategy for providing ventilation and space conditioning in buildings as part of the design of a HVAC system. UFAD systems use an underfloor supply plenum located between the structural co ...
*
Indoor air quality Indoor air quality (IAQ) is the air quality within and around buildings and structures. IAQ is known to affect the health, comfort, and well-being of building occupants. Poor indoor air quality has been linked to sick building syndrome, reduce ...
*
Thermal comfort Thermal comfort is the condition of mind that expresses satisfaction with the thermal environment and is assessed by subjective evaluation ( ANSI/ASHRAE Standard 55).ANSI/ASHRAE Standard 55-2017, Thermal Environmental Conditions for Human Occupan ...
*
Air conditioning Air conditioning, often abbreviated as A/C or AC, is the process of removing heat from an enclosed space to achieve a more comfortable interior environment (sometimes referred to as 'comfort cooling') and in some cases also strictly controlling ...
*
ASHRAE The American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE ) is an American professional association seeking to advance heating, ventilation, air conditioning and refrigeration (HVAC&R) systems design and constructi ...
*
SMACNA The Sheet Metal and Air Conditioning Contractors' National Association (SMACNA; pronounced 'Smack'-'Nah') is an international trade association with more than 4,500 contributing contractor members in 103 chapters throughout the United States, Can ...


References

{{Authority control Ventilation Heating, ventilation, and air conditioning