A fire alarm notification appliance is an
active fire protection Active fire protection (AFP) is an integral part of fire protection. AFP is characterized by items and/or systems, which require a certain amount of motion and response in order to work, contrary to passive fire protection. Categories of active fi ...
component of a
fire alarm system A fire alarm system warns people when smoke, fire, carbon monoxide or other fire-related or general notification emergency, emergencies are detected. These alarms may be activated automatically from smoke detectors and heat detectors or may also ...
. A notification appliance may use audible, visible, or other stimuli to alert the occupants of a fire or other emergency condition requiring action. Audible appliances have been in use longer than any other method of notification. Initially, all appliances were either electromechanical horns or
electric bell An electric bell is a mechanical or electronic bell that functions by means of an electromagnet. When an electric current is applied, it produces a repetitive buzzing, clanging or ringing sound. Electromechanical bells have been widely used at r ...
s, which would later be replaced by electronic sounders. Most of today's appliances produce sound pressure levels between 45 and 120
decibels The decibel (symbol: dB) is a relative unit of measurement equal to one tenth of a bel (B). It expresses the ratio of two values of a power or root-power quantity on a logarithmic scale. Two signals whose levels differ by one decibel have a ...
at ten feet.


Methods of notification

The primary function of the notification appliance is to alert persons at risk. Several methods are used and documented in industry specifications published by UL. Alerting methods include: * Sound (audible signals) ** ~3 kHz / ~3100 Hz tone (high frequency). Used in many current notification devices. ** 520 Hz (low frequency). Used in newer notification devices. ** 45 dB to 120 dB A weighted for human hearing (higher decibels, in the 100 to 120 dB range, were common with older electromechanical horns) * Light (visible signals) ** 15 cd to 1000 cd
candela The candela ( or ; symbol: cd) is the unit of luminous intensity in the International System of Units (SI). It measures luminous power per unit solid angle emitted by a light source in a particular direction. Luminous intensity is analogous t ...
output ** 1 to 2 flashes per second


Coding

Coding refers to the pattern or tones a notification appliance sounds in and is controlled either by the
panel Panel may refer to: Arts and media Visual arts *Panel (comics), a single image in a comic book, comic strip or cartoon; also, a comic strip containing one such image *Panel painting, in art, either one element of a multi-element piece of art, ...
or by setting jumpers or DIP switches on the notification appliances. The majority of audible notification appliances installed prior to 1996 produced a steady sound for evacuation. In general, no common standard at that time mandated any particular tone, or pattern for audible fire alarm evacuation signals. While less common than a steady sound, differing signaling methods were used for the same purpose. These are named with respect to their distinctive structure and include, March Time (usually 120 pulses per minute but sometimes at 90 pulses or 20 pulses per minute, depending on the panel), Hi-Lo (two different tones that alternate), Slow-Whoop (slow rising sweep upwards in tone) among others. Today these methods are confined to applications intended to trigger a response other than evacuation alone. In 1996, the
ANSI The American National Standards Institute (ANSI ) is a private non-profit organization that oversees the development of voluntary consensus standards for products, services, processes, systems, and personnel in the United States. The organi ...
and the NFPA recommended a standard evacuation pattern to eliminate confusion. The pattern is uniform without regard to the sound used. This pattern, which is also used for smoke alarms, is named the Temporal-Three alarm signal, often referred to as "T-3" or "Code-3" (ISO 8201 and ANSI/ASA S3.41 Temporal Pattern) and produces an interrupted four count (three half second pulses, followed by a one and one half second pause, repeated for a minimum of 180 seconds). CO (carbon monoxide) detectors are specified to use a similar pattern using four pulses of tone (often referred to as T4).


Audibility

From NFPA 72, 2002 Edition: “7.4.2.1* To ensure that audible public mode signals are clearly heard, unless otherwise permitted by 7.4.2.2 through 7.4.2.5, they shall have a sound level at least 15 dB (
Decibel The decibel (symbol: dB) is a relative unit of measurement equal to one tenth of a bel (B). It expresses the ratio of two values of a power or root-power quantity on a logarithmic scale. Two signals whose levels differ by one decibel have a ...
) above the average ambient sound level or 5 dB above the maximum sound level having a duration of at least 60 seconds, whichever is greater, measured 1.5 m (5 ft) above the floor in the occupiable area, using the A-weighted scale (dBA).”


Visual signals

In 1970, Space Age Electronics introduced the first visual notification appliance, the AV32 light plate (which was installed over an existing horn) and V33 remote light. Meanwhile, in 1976, Wheelock introduced the first horn/strobe notification appliances with its 700x series. The majority of visual signals throughout the 1970s and 1980s were white or red incandescent lights. In the 1980s, most new installations began to include visual signals, and more strobes started to appear. In the United States, the 1990
Americans with Disabilities Act The Americans with Disabilities Act of 1990 or ADA () is a civil rights law that prohibits discrimination based on disability. It affords similar protections against discrimination to Americans with disabilities as the Civil Rights Act of 1964 ...
(ADA) triggered changes in evacuation signaling methods to include the hearing impaired. Audible notification appliances would now have to include strobe lights with higher brightness intensity to alert the hearing impaired. This made incandescent lights inadequate for the purposes of the ADA. Many existing installations that did not include visual signals were retrofitted with strobe plates. These retrofit plates would allow for the easy installation of a strobe without replacing the audible signal. Later, ADA codes also required that strobes be at least 15 candelas and have a flash rate of at least 60 flashes per minute (one flash per second). Companies discontinued their translucent strobes, and replaced them with new, clear, high-intensity strobes. Today, strobe synchronization is often used to synchronize all strobes in a uniform flash pattern. This is to prevent individuals with
photosensitive epilepsy Photosensitive epilepsy (PSE) is a form of epilepsy in which seizures are triggered by visual stimuli that form patterns in time or space, such as flashing lights; bold, regular patterns; or regular moving patterns. PSE affects approximately o ...
from potentially experiencing seizures due to unsynchronized strobes.


Voice evacuation

Voice evacuation systems (also called Voice Alarm Systems) have become popular in most countries. Voice evacuation alarms typically are not as loud as horns or bells (although generally standards require the same minimum sound pressure levels), and usually sound an alarm tone (typically a slow whoop, code-3, or chime tone, although this depends on the country and particular application) and a voice message warning that an emergency has been reported and to evacuate the building (often also directing occupants to not use elevators). Voice evacuation systems can also be used by personnel to give specific live information and/or instructions over the alarm system using a built-in microphone, which provides a distinct advantage over horns or bells. The system can be stand alone (i.e. using dedicated loudspeakers, which can also feature integrated strobe lights), or the system can accommodate
public address system A public address system (or PA system) is an electronic system comprising microphones, amplifiers, loudspeakers, and related equipment. It increases the apparent volume (loudness) of a human voice, musical instrument, or other acoustic sound sou ...
functionality. In 1973, the
Autocall Autocall is a company that specializes in fire protection and customized communications equipment. The original company was founded in 1908 and was based in Shelby, Ohio. The Autocall brand became defunct in 2001 after it was incorporated into th ...
fire alarm company (merged to SimplexGrinnell then relaunched), manufactured the first voice evacuation system.


Voice evacuation in Europe

In Europe, voice evacuation systems are normally a mandatory requirement for rail and air transport terminals, high-rise buildings, schools, hospitals, and other large facilities. Voice systems for emergency use date back at least as far as the second world war. Following the lead of companies like Avalon, Tannoy and Millbank Electronics etc., in the 1980s many other companies such a
ASL
Application Solutions (Safety and Security) Ltd began producing voice-evacuation systems. In the 1990s, voice evacuation started to become the standard for large facilities, and is still growing in popularity. The use, design, operation and installation of Voice evacuation systems is governed in Europe by CENELEC European Committee for Electrotechnical Standardization EN 60849 and in the UK by the British Standard
BS 5839-Part 8 BS, B.S., Bs or bs may refer to: Arts and entertainment *BS-, a prefix for all games broadcast for the Satellaview modem via the Japanese Broadcasting Satellite system * "B.S." (song), a song by Jhené Aiko from the album ''Chilombo'' *Team BS ...
, a system code of practice. This is joined by the European harmonised equipment standards family
EN 54 The EN 54 Fire detection and fire alarm systems is a series of European standards that includes product standards and application guidelines for fire detection and fire alarm systems as well as voice alarm systems. The product standards defin ...
, and ISO 7240-16:2007.


Effectiveness

Initial research into the effectiveness of the various alerting methods is sparse. From 2005 to 2007, research sponsored by the NFPA focused on understanding the cause of a higher number of deaths seen in high-risk groups such as the elderly, those with hearing loss, and those who are intoxicated. Research findings suggest that a low frequency (520 Hz) square wave output is significantly more effective at waking high-risk individuals. More recent research suggests that strobe lights are not effective at waking sleeping adults with hearing loss and suggest that a different alarm tone is much more effective. Individuals in the hearing loss community are seeking changes to improved awakening methods.


Effectiveness of low frequency (520 Hz) sound

Further NFPA research demonstrated the heightened waking effectiveness of low frequency square wave auditory signals that use 520 Hz, especially when used to wake people with mild to moderately severe hearing loss. Two separate studies were conducted – one for the hard-of-hearing and one for the alcohol-impaired – in order to compare the waking effectiveness of 520 Hz low frequency square wave devices and 3100 Hz pure tone T-3 sound devices. Under the testing conditions, a 520 Hz square wave T-3 sound woke up 92% of hard-of-hearing participants, making it the most effective. The 3100 Hz pure tone T-3 sound woke up 56% of participants. A summary of the studies shows that the 520 Hz square wave signal has at least 4 to 12 times more waking effectiveness than the current 3100 Hz signal.


NFPA code implementation of low frequency (520 Hz) sound

Effective January 1, 2014, section 18.4.5.3 of the 2010 and later editions of NFPA 72 requires the low frequency audible fire alarm signal in occupancy sleeping areas with a protected premises (building) fire alarm system. The Chapter 18 committee chose to apply the requirement to all sleeping areas – not just those where occupants have self-identified as having a hearing impairment. This was done intentionally for several reasons: in many cases, the applications impacted are lodging spaces such as hotels, and many people may not know they have a hearing impairment or they may be alcohol impaired. The 520 Hz low frequency signal is required in sleeping areas of the following buildings: * Hotels and motels * College and university dormitories * Retirement/assisted-living facilities without trained staff responsible for waking up patients * Dwelling units within apartments and condominiums According to NFPA 72-2010, section 18.4.5.3*, audible appliances provided for sleeping areas to awaken occupants shall produce a low frequency alarm signal that complies with the following (effective January 1, 2014): * (1) The alarm signal shall be a square wave or provide equivalent awakening ability. * (2) The wave shall have a fundamental frequency of 520 Hz +/- 10 percent.


See also

*
Fire protection Fire protection is the study and practice of mitigating the unwanted effects of potentially destructive fires. It involves the study of the behaviour, compartmentalisation, suppression and investigation of fire and its related emergencies, as we ...
*
Active fire protection Active fire protection (AFP) is an integral part of fire protection. AFP is characterized by items and/or systems, which require a certain amount of motion and response in order to work, contrary to passive fire protection. Categories of active fi ...
*
Passive fire protection Passive fire protection (PFP) is components or systems of a building or structure that slows or impedes the spread of the effects of fire or smoke without system activation, and usually without movement. Examples of passive systems include floo ...
*
Fire alarm control panel A fire alarm control panel (FACP), fire alarm control unit (FACU), fire indicator panel (FIP), or simply fire alarm panel is the controlling component of a fire alarm system. The panel receives information from devices designed to detect and re ...
*
Fire alarm pull station Manual fire alarm activation is typically achieved through the use of a pull station (USA & Canada) or call point (Europe, Australia, and Asia), which then sounds the evacuation alarm for the relevant building or zone. Manual fire alarm ...
* Fire drill *
False alarm A false alarm, also called a nuisance alarm, is the deceptive or erroneous report of an emergency, causing unnecessary panic and/or bringing resources (such as emergency services) to a place where they are not needed. False alarms may occur with ...
*
Fire alarm system A fire alarm system warns people when smoke, fire, carbon monoxide or other fire-related or general notification emergency, emergencies are detected. These alarms may be activated automatically from smoke detectors and heat detectors or may also ...
*
Smoke detector A smoke detector is a device that senses smoke, typically as an indicator of fire. Smoke detectors are usually housed in plastic enclosures, typically shaped like a disk about in diameter and thick, but shape and size vary. Smoke can be detecte ...


References


Further reading

* National Fire Protection Code, Article 72 * Underwriters Laboratories UL 217: Single and Multiple Station Smoke Alarms * Underwriters Laboratories UL 1971: Signaling Devices for the Hearing Impaired


External links


National Fire Protection Association

NFPA study press release July 26, 2007: Effectiveness of audible and alternative non-audible alarms

Photosensitivity and Seizures resource at the Epilepsy Foundation

Hearing Loss Association of America press release: Current Smoke Alarm Unable To Wake Millions Of Hearing People

IMO/ISO 8201 Alarm Tone Table


* http://www.systemsensor.com/en-us/Files/Sound-Files/520-hz-tone-low-frequency.mp3
Fire Risk Guide
{{Authority control Fire detection and alarm ja:自動火災報知設備#地区音響装置