The stack effect or chimney effect is the movement of air into and out of buildings through unsealed openings,
chimney A chimney is an architectural ventilation structure made of masonry, clay or metal that isolates hot toxic exhaust gases or smoke produced by a boiler, stove, furnace, incinerator, or fireplace from human living areas. Chimneys are typ ...
s, flue-gas stacks, or other containers, resulting from air
buoyancy Buoyancy (), or upthrust, is an upward force exerted by a fluid that opposes the weight of a partially or fully immersed object. In a column of fluid, pressure increases with depth as a result of the weight of the overlying fluid. Thus the ...
. Buoyancy occurs due to a difference in indoor-to-outdoor
air density The density of air or atmospheric density, denoted '' ρ'', is the mass per unit volume of Earth's atmosphere. Air density, like air pressure, decreases with increasing altitude. It also changes with variation in atmospheric pressure, temperature a ...
resulting from temperature and moisture differences. The result is either a positive or negative buoyancy force. The greater the thermal difference and the height of the structure, the greater the buoyancy force, and thus the stack effect. The stack effect helps drive
natural ventilation Passive ventilation is the process of supplying air to and removing air from an indoor space without using mechanical systems. It refers to the flow of external air to an indoor space as a result of pressure differences arising from natural force ...
,
air infiltration Infiltration is the unintentional or accidental introduction of outside air into a building, typically through cracks in the building envelope and through use of doors for passage. Infiltration is sometimes called air leakage. The leakage of room ...
, and fires (e.g. the Kaprun tunnel fire, King's Cross underground station fire and the
Grenfell Tower fire On 14 June 2017, a high-rise fire broke out in the 24-storey Grenfell Tower block of flats in North Kensington, West London, at 00:54 BST and burned for 60 hours. 72 people died, two later in hospital, with more than 70 injured and 223 esca ...
).


Stack effect in buildings

Since buildings are not totally sealed (at the very minimum, there is always a ground level entrance), the stack effect will cause air infiltration. During the heating season, the warmer indoor air rises up through the building and escapes at the top either through open windows, ventilation openings, or unintentional holes in ceilings, like ceiling fans and recessed lights. The rising warm air reduces the
pressure Pressure (symbol: ''p'' or ''P'') is the force applied perpendicular to the surface of an object per unit area over which that force is distributed. Gauge pressure (also spelled ''gage'' pressure)The preferred spelling varies by country a ...
in the base of the building, drawing cold air in through either open doors, windows, or other openings and leakage. During the cooling season, the stack effect is reversed, but is typically weaker due to lower temperature differences. In a modern
high-rise building A tower block, high-rise, apartment tower, residential tower, apartment block, block of flats, or office tower is a tall building, as opposed to a low-rise building and is defined differently in terms of height depending on the jurisdicti ...
with a well-sealed
envelope An envelope is a common packaging item, usually made of thin, flat material. It is designed to contain a flat object, such as a letter or card. Traditional envelopes are made from sheets of paper cut to one of three shapes: a rhombus, a ...
, the stack effect can create significant pressure differences that must be given design consideration and may need to be addressed with mechanical
ventilation Ventilation may refer to: * Ventilation (physiology), the movement of air between the environment and the lungs via inhalation and exhalation ** Mechanical ventilation, in medicine, using artificial methods to assist breathing *** Ventilator, a m ...
. Stairwells, shafts, elevators, and the like, tend to contribute to the stack effect, while interior partitions, floors, and fire separations can mitigate it. Especially in case of fire, the stack effect needs to be controlled to prevent the spread of smoke and fire, and to maintain tenable conditions for occupants and firefighters. While natural ventilation methods may be effective, such as air outlets being installed closer to the ground, mechanical ventilation is often preferred for taller structures or in buildings with limited space. Smoke extraction is a key consideration in new constructions and must be evaluated in design stages. The
Grenfell Tower fire On 14 June 2017, a high-rise fire broke out in the 24-storey Grenfell Tower block of flats in North Kensington, West London, at 00:54 BST and burned for 60 hours. 72 people died, two later in hospital, with more than 70 injured and 223 esca ...
, as a result of which 71 people died, was in part exacerbated by the stack effect. A cavity between the outer aluminium cladding and the inner insulation formed a chimney and drew the fire upwards.


Normal and reverse stack effect

Two regimes of stack effect can exist in buildings: normal and reverse. Normal stack effect occurs in buildings which are maintained at a higher temperature than the outdoor environment. Warm air within the building has a low density (or high specific volume) and exhibits a greater buoyancy force. Consequently, it rises from lower levels to upper levels through penetrations between floors. This presents a situation where floors underneath the neutral axis of the building have a net negative pressure, whereas floors above the neutral axis have a net positive pressure. The net negative pressure on lower floors can induce outdoor air to infiltrate the building through doors, windows, or ductwork without backdraft dampers. Warm air will attempt to exfiltrate the building envelope through floors above the neutral axis. Mechanical refrigeration equipment provides sensible and latent cooling during summer months. This reduces the dry-bulb temperature of the air within the building relative to the outdoor ambient air. It also decreases the specific volume of the air contained within the building, thereby reducing the buoyancy force. Consequently, cool air will travel vertically down the building through elevator shafts, stairwells, and unsealed utility penetrations (i.e.,
hydronics Hydronics () is the use of liquid water or gaseous water ( steam) or a water solution (usually glycol with water) as heat-transfer medium in heating and cooling systems. The name differentiates such systems from oil and refrigerant systems ...
, electric and water risers). Once the conditioned air reaches the bottom floors underneath the neutral axis, it exfiltrates the building envelopes through unsealed openings such as through dampers, curtainwall, etc. The exfiltrating air on floors underneath the neutral axis will induce outdoor air to infiltrate the building envelope through unsealed openings.


Stack effect in flue gas stacks and chimneys

The stack effect in industrial flue gas stacks is similar to that in buildings, except that it involves hot
flue A flue is a duct, pipe, or opening in a chimney for conveying exhaust gases from a fireplace, furnace, water heater, boiler, or generator to the outdoors. Historically the term flue meant the chimney itself. In the United States, they are ...
gases having large temperature differences with the ambient outside air. Furthermore, an industrial flue gas stack typically provides little obstruction for the flue gas along its length and is, in fact, normally optimized to enhance the stack effect to reduce fan energy requirements. Large temperature differences between the outside air and the flue gases can create a strong stack effect in
chimneys A chimney is an architectural ventilation structure made of masonry, clay or metal that isolates hot toxic exhaust gases or smoke produced by a boiler, stove, furnace, incinerator, or fireplace from human living areas. Chimneys are typ ...
for buildings using a
fireplace A fireplace or hearth is a structure made of brick, stone or metal designed to contain a fire. Fireplaces are used for the relaxing ambiance they create and for heating a room. Modern fireplaces vary in heat efficiency, depending on the desig ...
for heating. Before the development of large volume fans, mines were ventilated using the stack effect. A downcast shaft allowed air into the mine. At the foot of the upcast shaft a furnace was kept continuously burning. The shaft (commonly several hundred yards deep) behaved like a chimney and air rose through it drawing fresh air down the downcast stack and around the mine.


Cause for the stack effect

There is a pressure difference between the outside air and the air inside the building caused by the difference in temperature between the outside air and the inside air. That pressure difference ( ''ΔP'' ) is the driving force for the stack effect and it can be calculated with the equations presented below. The equations apply only to buildings where air is both inside and outside the buildings. For buildings with one or two floors, ''h'' is the height of the building. For multi-floor, high-rise buildings, ''h'' is the distance from the openings at the neutral pressure level (NPL) of the building to either the topmost openings or the lowest openings. Reference explains how the NPL affects the stack effect in high-rise buildings. For flue gas stacks and chimneys, where air is on the outside and combustion flue gases are on the inside, the equations will only provide an approximation and ''h'' is the height of the flue gas stack or chimney. :\Delta P = C a h \bigg(\frac - \frac \bigg) :
SI units The International System of Units, known by the international abbreviation SI in all languages and sometimes pleonastically as the SI system, is the modern form of the metric system and the world's most widely used system of measurement. ...
: : : U.S. customary units: :


Induced flow

The draft (draught in
British English British English (BrE, en-GB, or BE) is, according to Oxford Dictionaries, "English as used in Great Britain, as distinct from that used elsewhere". More narrowly, it can refer specifically to the English language in England, or, more broadl ...
) flow rate induced by the stack effect can be calculated with the equation presented below. The equation applies only to buildings where air is both inside and outside the buildings. For buildings with one or two floors, ''h'' is the height of the building and ''A'' is the flow area of the openings. For multi-floor, high-rise buildings, ''A'' is the flow area of the openings and ''h'' is the distance from the openings at the neutral pressure level (NPL) of the building to either the topmost openings or the lowest openings. Reference explains how the NPL affects the stack effect in high-rise buildings. For flue gas stacks or chimneys, where air is on the outside and combustion flue gases are on the inside, the equation will only provide an approximation. Also, ''A'' is the cross-sectional flow area and ''h'' is the height of the flue gas stack or chimney. :Q = C A \sqrt :
SI units The International System of Units, known by the international abbreviation SI in all languages and sometimes pleonastically as the SI system, is the modern form of the metric system and the world's most widely used system of measurement. ...
: : : U.S. customary units: : This equation assumes that the resistance to the draft flow is similar to the resistance of flow through an orifice characterized by a discharge coefficient ''C''.


See also

*
HVAC Heating, ventilation, and air conditioning (HVAC) is the use of various technologies to control the temperature, humidity, and purity of the air in an enclosed space. Its goal is to provide thermal comfort and acceptable indoor air quality. ...
(heating, ventilation and air conditioning) *
Ventilation shaft In subterranean civil engineering, ventilation shafts, also known as airshafts or vent shafts, are vertical passages used in mines and tunnels to move fresh air underground, and to remove stale air. In architecture, an airshaft is a small, ...
* Solar chimney *
Solar updraft tower The solar updraft tower (SUT) is a design concept for a renewable-energy power plant for generating electricity from low temperature solar heat. Sunshine heats the air beneath a very wide greenhouse-like roofed collector structure surrounding ...
*
Draft (boiler) The difference between atmospheric pressure and the pressure existing in the furnace or flue gas passage of a boiler is termed as draft. Draft can also be referred to as the difference in pressure in the combustion chamber area which results in the ...
*
Inco Superstack The Inco Superstack in Sudbury, Ontario, with a height of , is the tallest chimney in Canada and the Western hemisphere, and the second tallest freestanding chimney in the world after the GRES-2 Power Station in Kazakhstan. It is also the s ...
*
Ekibastuz GRES-2 Power Station Ekibastuz ( kk, Екібастұз, translit=Ekıbastūz, , ەكئباستۇز; russian: Экибастуз) is a city in Pavlodar Region, northeastern Kazakhstan. The population was Ekibastuz is served by Ekibastuz Airport. History The history ...
*
Windcatcher A windcatcher, wind tower, or wind scoop ( ar, برجيل ; fa, بادگیر) is a traditional architectural element used to create cross ventilation and passive cooling in buildings. Windcatchers come in various designs: unidirectional, bi ...
* Cross ventilation


References


External links


Stack Effect: When Buildings Act Like Chimneys --Green Building Advisor