In the power systems analysis field of
electrical engineering Electrical engineering is an engineering discipline concerned with the study, design, and application of equipment, devices, and systems which use electricity, electronics, and electromagnetism. It emerged as an identifiable occupation in the l ...
, a per-unit system is the expression of system quantities as fractions of a defined base unit quantity. Calculations are simplified because quantities expressed as per-unit do not change when they are referred from one side of a transformer to the other. This can be a pronounced advantage in power system analysis where large numbers of transformers may be encountered. Moreover, similar types of apparatus will have the impedances lying within a narrow numerical range when expressed as a per-unit fraction of the equipment rating, even if the unit size varies widely. Conversion of per-unit quantities to volts, ohms, or amperes requires a knowledge of the base that the per-unit quantities were referenced to. The per-unit system is used in power flow,
short circuit A short circuit (sometimes abbreviated to short or s/c) is an electrical circuit that allows a current to travel along an unintended path with no or very low electrical impedance. This results in an excessive current flowing through the circuit ...
evaluation, motor starting studies etc. The main idea of a per unit system is to absorb large differences in absolute values into base relationships. Thus, representations of elements in the system with per unit values become more uniform. A per-unit system provides units for
power Power most often refers to: * Power (physics), meaning "rate of doing work" ** Engine power, the power put out by an engine ** Electric power * Power (social and political), the ability to influence people or events ** Abusive power Power may ...
,
voltage Voltage, also known as electric pressure, electric tension, or (electric) potential difference, is the difference in electric potential between two points. In a static electric field, it corresponds to the work needed per unit of charge to ...
, current, impedance, and
admittance In electrical engineering, admittance is a measure of how easily a circuit or device will allow a current to flow. It is defined as the reciprocal of impedance, analogous to how conductance & resistance are defined. The SI unit of admittan ...
. With the exception of impedance and admittance, any two units are independent and can be selected as base values; power and voltage are typically chosen. All quantities are specified as multiples of selected base values. For example, the base power might be the rated power of a
transformer A transformer is a passive component that transfers electrical energy from one electrical circuit to another circuit, or multiple circuits. A varying current in any coil of the transformer produces a varying magnetic flux in the transformer's ...
, or perhaps an arbitrarily selected power which makes power quantities in the system more convenient. The base voltage might be the nominal voltage of a
bus A bus (contracted from omnibus, with variants multibus, motorbus, autobus, etc.) is a road vehicle that carries significantly more passengers than an average car or van. It is most commonly used in public transport, but is also in use for ch ...
. Different types of quantities are labeled with the same symbol (pu); it should be clear whether the quantity is a voltage, current, or other unit of measurement.


Purpose

There are several reasons for using a per-unit system: * Similar apparatus (generators, transformers, lines) will have similar per-unit impedances and losses expressed on their own rating, regardless of their absolute size. Because of this, per-unit data can be checked rapidly for gross errors. A per unit value out of normal range is worth looking into for potential errors. * Manufacturers usually specify the impedance of apparatus in per unit values. * Use of the constant \textstyle \sqrt is reduced in three-phase calculations. * Per-unit quantities are the same on either side of a transformer, independent of voltage level * By normalizing quantities to a common base, both hand and automatic calculations are simplified. * It improves numerical stability of automatic calculation methods. * Per unit data representation yields important information about relative magnitudes. The per-unit system was developed to make manual analysis of power systems easier. Although power-system analysis is now done by computer, results are often expressed as per-unit values on a convenient system-wide base.


Base quantities

Generally base values of power and voltage are chosen. The base power may be the rating of a single piece of apparatus such as a motor or generator. If a system is being studied, the base power is usually chosen as a convenient round number such as 10 MVA or 100 MVA. The base voltage is chosen as the nominal rated voltage of the system. All other base quantities are derived from these two base quantities. Once the base power and the base voltage are chosen, the base current and the base impedance are determined by the natural laws of electrical circuits. The base value should only be a magnitude, while the per-unit value is a phasor. The phase angles of complex power, voltage, current, impedance, etc., are not affected by the conversion to per unit values. The purpose of using a per-unit system is to simplify conversion between different transformers. Hence, it is appropriate to illustrate the steps for finding per-unit values for voltage and impedance. First, let the base power (''S'') of each end of a transformer become the same. Once every ''S'' is set on the same base, the base voltage and base impedance for every transformer can easily be obtained. Then, the real numbers of impedances and voltages can be substituted into the per-unit calculation definition to get the answers for the per-unit system. If the per-unit values are known, the real values can be obtained by multiplying by the base values. By convention, the following two rules are adopted for base quantities: * The base power value is the same for the entire power system of concern. * The ratio of the voltage bases on either side of a transformer is selected to be the same as the ratio of the transformer voltage ratings. With these two rules, a per-unit impedance remains unchanged when referred from one side of a transformer to the other. This allows the ideal transformer to be eliminated from a transformer model.


Relationship between units

The relationship between units in a per-unit system depends on whether the system is single-phase or
three-phase Three-phase electric power (abbreviated 3φ) is a common type of alternating current used in electricity generation, transmission, and distribution. It is a type of polyphase system employing three wires (or four including an optional neutral ...
.


Single-phase

Assuming that the independent base values are power and voltage, we have: : P_ = 1 \text : V_ = 1 \text Alternatively, the base value for power may be given in terms of
reactive Reactive may refer to: *Generally, capable of having a reaction (disambiguation) *An adjective abbreviation denoting a bowling ball coverstock made of reactive resin * Reactivity (chemistry) *Reactive mind *Reactive programming See also *Reactan ...
or
apparent power Apparent may refer to: * Apparent magnitude, a measure of brightness of a celestial body as seen by an observer on Earth * Apparent places, the actual coordinates of stars as seen from Earth * Heir apparent, a person who is first in line of succes ...
, in which case we have, respectively, : Q_ = 1 \text or : S_ = 1 \text The rest of the units can be derived from power and voltage using the equations S = IV, P = S\cos(\phi), Q = S\sin(\phi) and \underline = \underline \underline (
Ohm's law Ohm's law states that the current through a conductor between two points is directly proportional to the voltage across the two points. Introducing the constant of proportionality, the resistance, one arrives at the usual mathematical equa ...
), Z being represented by \underline = R + j X = Z\cos(\phi) + j Z\sin(\phi). We have: : I_ = \frac = 1 \text : Z_ = \frac = \frac = \frac = 1 \text : Y_ = \frac = 1 \text


Three-phase

Power and voltage are specified in the same way as single-phase systems. However, due to differences in what these terms usually represent in three-phase systems, the relationships for the derived units are different. Specifically, power is given as total (not per-phase) power, and voltage is line-to-line voltage. In three-phase systems the equations P = S\cos(\phi) and Q = S\sin(\phi) also hold. The apparent power S now equals S_= \sqrtV_ I_ : I_ = \frac = 1 \text : Z_ = \frac = \frac = 1 \text : Y_ = \frac = 1 \text


Example of per-unit

As an example of how per-unit is used, consider a three-phase power transmission system that deals with powers of the order of 500 MW and uses a nominal voltage of 138 kV for transmission. We arbitrarily select S_ = 500\, \mathrm, and use the nominal voltage 138 kV as the base voltage V_. We then have: : I_ = \frac = 2.09 \, \mathrm : Z_ = \frac = \frac = 38.1 \, \Omega : Y_ = \frac = 26.3 \, \mathrm If, for example, the actual voltage at one of the buses is measured to be 136 kV, we have: : V_ = \frac = \frac = 0.9855 \, \mathrm


Per-unit system formulas

The following tabulation of per-unit system formulas is adapted from Beeman's ''Industrial Power Systems Handbook''.


In transformers

It can be shown that voltages, currents, and impedances in a per-unit system will have the same values whether they are referred to primary or secondary of a
transformer A transformer is a passive component that transfers electrical energy from one electrical circuit to another circuit, or multiple circuits. A varying current in any coil of the transformer produces a varying magnetic flux in the transformer's ...
. For instance, for voltage, we can prove that the per unit voltages of two sides of the transformer, side 1 and side 2, are the same. Here, the per-unit voltages of the two sides are ''E''1pu and ''E''2pu respectively. : \begin E_\text&=\frac\\ &= \frac \\ &= \frac \\ &= \frac \\ &= E_\text\\ \end (source: Alexandra von Meier Power System Lectures, UC Berkeley) ''E''1 and ''E''2 are the voltages of sides 1 and 2 in volts. ''N''1 is the number of turns the coil on side 1 has. ''N''2 is the number of turns the coil on side 2 has. ''V''base1 and ''V''base2 are the base voltages on sides 1 and 2. : V_\text=\fracV_\text For current, we can prove that the per-unit currents of the two sides are the same below. : \begin I_\text&=\frac\\ &= \frac \\ &= \frac \\ &= \frac \\ &= I_\text\\ \end (source: Alexandra von Meier Power System Lectures, UC Berkeley) where ''I''1,pu and ''I''2,pu are the per-unit currents of sides 1 and 2 respectively. In this, the base currents ''I''base1 and ''I''base2 are related in the opposite way that ''V''base1 and Vbase2 are related, in that : \begin I_\text &= \frac \\ S_\text &= S_\text\\ V_\text &= \frac V_\text\\ I_\text &= \frac \\ I_\text &= \frac \\ &= \frac I_\text\\ \end The reason for this relation is for power conservation :''S''base1 = ''S''base2 The full load copper loss of a transformer in per-unit form is equal to the per-unit value of its resistance: \begin P_\text&=\text\\ &= I_^2R_\\ \end \begin P_\text&=\frac\\ &= \frac \\ &= \frac \\ &= \frac \\ &= R_\text\\ \end Therefore, it may be more useful to express the resistance in per-unit form as it also represents the full-load copper loss. As stated above, there are two degrees of freedom within the per unit system that allow the engineer to specify any per unit system. The degrees of freedom are the choice of the base voltage (''V'') and the base power (''S''). By convention, a single base power (''S'') is chosen for both sides of the transformer and its value is equal to the rated power of the transformer. By convention, there are actually two different base voltages that are chosen, ''V'' and ''V'' which are equal to the rated voltages for either side of the transformer. By choosing the base quantities in this manner, the transformer can be effectively removed from the circuit as described above. For example: Take a transformer that is rated at 10 kVA and 240/100 V. The secondary side has an impedance equal to 1∠0° Ω. The base impedance on the secondary side is equal to: \begin Z_\text&=\frac\\ &= \frac \\ &= \text\Omega\\ \end This means that the per unit impedance on the secondary side is 1∠0° Ω / 1 Ω = 1∠0° pu When this impedance is referred to the other side, the impedance becomes: \begin Z_&=\left(\frac\right)^2\times\text\Omega\\ &= \text \Omega\\ \end The base impedance for the primary side is calculated the same way as the secondary: \begin Z_\text&=\frac\\ &= \frac \\ &= \text\Omega\\ \end This means that the per unit impedance is 5.76∠0° Ω / 5.76 Ω = 1∠0° pu, which is the same as when calculated from the other side of the transformer, as would be expected. Another useful tool for analyzing transformers is to have the base change formula that allows the engineer to go from a base impedance with one set of a base voltage and base power to another base impedance for a different set of a base voltage and base power. This becomes especially useful in real life applications where a transformer with a secondary side voltage of 1.2 kV might be connected to the primary side of another transformer whose rated voltage is 1 kV. The formula is as shown below. \begin Z_\text&=Z_\text \times \frac=Z_\text \times \left(\frac\right)^2\times\left(\frac\right)\\ \end


References

* * * * * *{{cite book, last1=Glover, first1=J. Duncan, last2=Sarma, first2=Mulukutla, last3=Overbye, first3=Thomas J., title=Power System Analysis and Design, year=2011, publisher=Cengage Learning, isbn=978-1111425777, pages=108–116, url=https://books.google.com/books?id=U77A2C37QesC&q=power+system+analysis+and+design Electrical engineering Electric power Power engineering